Supported Windows versions: NT 4.0
Use these setting when using the SST 5136 SD ISA or SST 5136 SD PCI bus card to communicate Data Highway Plus to PLC-5 controllers, SLC 5/04 controllers.
· Select the Adapter
· Enabled = CHECKED
· Device Type = SST 5136
· SST 5136 SD ISA Cards
Enter a Base Address
Enter the IO Port Address assigned to the card.
· SST 5136 SD PCI Cards
Use the Base Address and IO Port settings from SD Card Manager
· Select PLCType
PLC-5 Family - when communicating to Allen-Bradley PLC-5 Style Processors
SLC 5/04 via DH+ - when communicating to Allen-Bradley SLC 5/04 Processors.
· Select Link Speed = 57.6K, 115.2K, or 230K
LinkSpeed must match the baud rate of the DataHighway Plus network.
· TimeOut (3000ms) default. This is how long the INGEAR driver will wait for a response after sending a message on the DataHighway Plus network.
· Station ID – This is the DataHighway Plus network node number you are assigning to the SST 5136 card.
The Station ID must be a unique number on the DataHighway Plus network.
· Term Name (Optional) – This is a 7 character user defined string to identify the SST 5136 card to other nodes on the DataHighway Plus network.
· Click Apply
· Click Done
Notes:
All other driver settings are not used for this configuration.
Addressing individual nodes on the DataHighway Plus network is done via the INGEAR PLC ActiveX control properties