ControlLogix Gateway to DH+

Select the Driver you created for the ControlLogix/CompactLogix.

 

Setting the PLC Type

If you’re communicating to a PLC-5 processor, select PLC-5 Family

images\img00750.gif

If you’re communicating to a SLC 5/04 processor, select SLC Enhanced

images\img00751.gif

 

Setting the Route Path

1.<slot>.<channel>.(DH+ Node)

1.

First segment:
Backplane (always 1.) of the local chassis

<slot>.

Second segment :
Slot of the 1756-DH+RIO module

<channel>.

Third segment:
A. or B. (Channel A or B)

(DH+ node)

Fourth segment:
This DH+ Node address of PLC (decimal value)

Example: Slot 3 (1756-DH+RIO)->Channel B ~~~ DH+ Node 7

images\img00752.gif

Also See: Hot Switch PLC Nodes

1. – Backplane
3. – 1756-DH+RIO slot
B. – Channel B
7 – PLC DH+ Address